Issue
Need a method for importing Concept Programming software variables into Vijeo Designer.
Product line
Concept, Vijeo Designer
Resolution
Need a method for importing Concept Programming software variables into Vijeo Designer.
Product line
Concept, Vijeo Designer
Resolution
- Export Concept variables to a TXT file.
- Rename from a TXT to a CCN file extension.
- In Vijeo Designer, Right-click on the variable section and select link variables.
- If changes are required, select Update variables.
Опубліковано для:Schneider Electric Україна

