Пошук серед найпопулярніших питань
HORB COMMUNICATION
Issue
Cannot display persistent variable in the embedded web page of some factory cast modules when opening Data editor, graphic viewer and graphic editor
Product Line
Factory cast HMI (WMY, NMW), Factory cast gateway (TSXETG30xx)
Resolution
Additional Information
Principle of HORB communication
Cannot display persistent variable in the embedded web page of some factory cast modules when opening Data editor, graphic viewer and graphic editor
Product Line
Factory cast HMI (WMY, NMW), Factory cast gateway (TSXETG30xx)
Resolution
- HORB communication is only used for FactoryCast HMI module (WMY, NWM) and FactoryCast Gateway (TSXETG30xx), not for others FactoryCast modules (NOE, ETY, ETG1000 ...)
- For FactoryCast HMI modules : all the variables are persistent; for FactoryCast modules: all the variables are non-persistent; for FactoryCast Gateway modules (TSXETG30xx): we can have both persistent and non persistent variables.
- When we want to display persistent variables in the embedded web page of the FactoryCast gateway (TSXETG30xx) module, only the data editor lite will display those variable because it uses the ModbusTCP/IP communication (port502). For persistent or non-persistent variables, the data editor, Graphic viewer and Graphic editor do not use the same communication protocol:
Additional Information
Principle of HORB communication
Опубліковано для:Schneider Electric Україна
Досліджуйте більше
Серія:
Досліджуйте більше
Серія: