Issue:
Output measured (KW) in the ATV61
Product Line:
ATV61 / ATV71
Environment:
All
Cause:
NA
Resolution:
The power of motor is not measured by the drive. It is calculated from the measurement of motor current and the output speed (estimated in open load and measured in closed loop).
OPR = (Iq / Iqn) * (Spd / Nn) * (PhirdRef / Phirn) in %
With: Iq : Current torque provide by the command to drive motor
PhirdRef : Flux provide by the command to drive motor
Iqn : Nominal Current torque compute with the motor name plate
Spd : Spd of the rotor, estimated or measured
Nn : Nominal speed of motor name plate
Phirn : Nominal flux of the motor
The accuracy of motor power is around 10%.
Output measured (KW) in the ATV61
Product Line:
ATV61 / ATV71
Environment:
All
Cause:
NA
Resolution:
The power of motor is not measured by the drive. It is calculated from the measurement of motor current and the output speed (estimated in open load and measured in closed loop).
OPR = (Iq / Iqn) * (Spd / Nn) * (PhirdRef / Phirn) in %
With: Iq : Current torque provide by the command to drive motor
PhirdRef : Flux provide by the command to drive motor
Iqn : Nominal Current torque compute with the motor name plate
Spd : Spd of the rotor, estimated or measured
Nn : Nominal speed of motor name plate
Phirn : Nominal flux of the motor
The accuracy of motor power is around 10%.
Опубліковано для:Schneider Electric Україна



