Issue
Opening a Unity pro STA application built with LL984 library in Unity pro 10, generates these kinds of warnings:
LL_SENS_I Type not found in Types Library,
LL_UCTR Type not found in Types Library,
LL_T01 Type not found in Types Library,
LL_T001 Type not found in Types Library
Product Line
Unity
Resolution
- install the LL984 library with the according Unity version
- open the unity STA file in Unity 10
- export the XEF or ZEF
- import the XEF or ZEF
- build the project.
Opening a Unity pro STA application built with LL984 library in Unity pro 10, generates these kinds of warnings:
LL_SENS_I Type not found in Types Library,
LL_UCTR Type not found in Types Library,
LL_T01 Type not found in Types Library,
LL_T001 Type not found in Types Library
Product Line
Unity
Resolution
- install the LL984 library with the according Unity version
- open the unity STA file in Unity 10
- export the XEF or ZEF
- import the XEF or ZEF
- build the project.
Опубліковано для:Schneider Electric Україна

