How can one configure the ATV312 to run upon power up and ramp up to full speed (60 hz)?

Issue:
ATV312 set up configuration to run upon power up and ramp up to full speed (60 hz).

Product Line:
Altivar 312, ATV312

Environment:
N/A

Cause:
N/A

Resolution:
Go into I-0- menu.
Set TCC to 2C.
Set TCT to LEL.

Go into SET- menu.
Set LSP to value desired in hz.  For example, 60 hz is full speed.

Once programming is complete and drive powered down apply jumper to LI1 and +24V for run command.
Note: Drive will run motor as soon as power is applied to the drive with this configuration.