{}

Наші бренди

Impact-Company-Logo-English Black-01-177x54

Вітаємо на веб-сайті Schneider Electric

Ласкаво просимо на наш веб-сайт.

Пошук серед найпопулярніших питань

Do you recommend non-shielded cable over shielded cable for longer drive to motor leads?

Issue:
Is shielded or non-shielded cable recommended for longer motor leads?

Product Line:
Altivar drives

Environment:
All model numbers

Cause:
N/A

Resolution:
A shielded cable will have more stray capacitance to ground as compared to a non-shielded cable.
So the longer the shielded cable the more leakage current that can occur to ground.
This leakage current can cause nuisance ground detection faults.

Schneider Electric Украина

Досліджуйте більше
Серія:
Altivar 61Altivar 71Altivar Process ATV600Altivar Process ATV900Altivar 12
Досліджуйте більше
Серія:
Altivar 61Altivar 71Altivar Process ATV600Altivar Process ATV900Altivar 12