Пошук серед найпопулярніших питань
How and why are the Altistart Softstarts and Altivar AC Drives de-rated for altitude?
Issue:
Altistart Softstarts and Altivar AC Drives de-rated for altitude
Product Line:
Altivar AC Drive Altistart Softstarts
Environment:
All
Cause:
NA
Resolution:
As altitude increases, lower air pressure results in lower air density and the cooling is less efficient.
There is also a maximum limit. This is due to the reduced air electrical resistance, which requires larger spacing to prevent arcing. The circuit boards and component spacing allows only up to a maximum altitude.
For Altistart Softstarts the Maximum Operating Altitude; 3300 ft (1000 m) without de-rating. Above this, de-rate the nominal current by 2.2% for each additional 330 ft (100 m) to a maximum of 6600 ft (2000 m).
For AC Altivar and Process Drives - Consult the appropriate Installation manuals since derating varies by Installation features and frame size.
Altistart Softstarts and Altivar AC Drives de-rated for altitude
Product Line:
Altivar AC Drive Altistart Softstarts
Environment:
All
Cause:
NA
Resolution:
As altitude increases, lower air pressure results in lower air density and the cooling is less efficient.
There is also a maximum limit. This is due to the reduced air electrical resistance, which requires larger spacing to prevent arcing. The circuit boards and component spacing allows only up to a maximum altitude.
For Altistart Softstarts the Maximum Operating Altitude; 3300 ft (1000 m) without de-rating. Above this, de-rate the nominal current by 2.2% for each additional 330 ft (100 m) to a maximum of 6600 ft (2000 m).
For AC Altivar and Process Drives - Consult the appropriate Installation manuals since derating varies by Installation features and frame size.
Опубліковано для:Schneider Electric Украина
Досліджуйте більше
Категорія:
Досліджуйте більше
Категорія: