Issue:
Wondering how do you program an ATV630, to replace an ATV58, in a Trane Air Handler
Product Line:
ATV630
Environment:
All
Cause:
Wiring and programming
Resolution:
A Trane Unit had a board that did the switching for the drive. If you've wired exactly as before, you only need to Program [Complete settings] > [Command and Reference] > [Ref Freq.1Cfg] to AI1 and [Complete Settings] [Input/Output] [R2 Configuration] to Drive Running. Be sure to configure [Simply Start].
Wondering how do you program an ATV630, to replace an ATV58, in a Trane Air Handler
Product Line:
ATV630
Environment:
All
Cause:
Wiring and programming
Resolution:
A Trane Unit had a board that did the switching for the drive. If you've wired exactly as before, you only need to Program [Complete settings] > [Command and Reference] > [Ref Freq.1Cfg] to AI1 and [Complete Settings] [Input/Output] [R2 Configuration] to Drive Running. Be sure to configure [Simply Start].
Опубліковано для:Schneider Electric Україна

