Can I control the number of automatic restart attempts on my LTMR after a voltage dip condition has been detected?
Issue:
Need to limit the number of automatic restart attempts after a voltage dip condition occurs.

Product line:
LTMR Tesys T

Environment:
All models with LTM-E expansion module attached.

Cause:
Information is unclear in the current literature.

Resolution:
It is not possible to limit the number of restart attempts in the LTMR to a specific number of attempts.  The function can be disabled, set to "load shedding" mode, or set to automatic restart.  The function requires an LTM-E expansion module, it is not present in the LTMR without the expansion module attached.

There are three registers in the LTMR that track the number of restart attempts, depending on what type of restart occurred:

Auto Restart Immediate count: When a voltage dip occurs but the voltage returns to normal quickly (within the time set by the parameter " Auto restart immediate timeout" the LTMR will perform an immediate restart and increment the "Auto restart immediate count" by one.

Auto Restart Delayed count:  When a voltage dip occurs and the voltage remains low for an extended time (longer than the "Auto Restart Immediate Timeout" parameter) the LTMR will wait to attempt to restart the motor.  The amount of time the LTMR waits before attempting restart is set via the "Auto restart delayed timeout" parameter.  Once a delayed restart occurs, the LTMR increments the "Auto Restart Delayed Count" by one.

Auto Restart Manual Count:  If a voltage dip occurs and the voltage remains low for a time greater than "Voltage Dip Restart timeout" then an auto restart will not occur.  It will be necessary to cycle the run command to the LTMR in order to restart.   The LTMR records the number of times this occurs under the parameter "Auto Restart Manual Count".

Schneider Electric Україна

Can I control the number of automatic restart attempts on my LTMR after a voltage dip condition has been detected?
Issue:
Need to limit the number of automatic restart attempts after a voltage dip condition occurs.

Product line:
LTMR Tesys T 

Environment:
All models with LTM-E expansion module attached.

Cause:
Information is unclear in the current literature.

Resolution:
It is not possible to limit the number of restart attempts in the LTMR to a specific number of attempts.  The function can be disabled, set to "load shedding" mode, or set to automatic restart.  The function requires an LTM-E expansion module, it is not present in the LTMR without the expansion module attached.

There are three registers in the LTMR that track the number of restart attempts, depending on what type of restart occurred:

Auto Restart Immediate count: When a voltage dip occurs but the voltage returns to normal quickly (within the time set by the parameter " Auto restart immediate timeout" the LTMR will perform an immediate restart and increment the "Auto restart immediate count" by one.

Auto Restart Delayed count:  When a voltage dip occurs and the voltage remains low for an extended time (longer than the "Auto Restart Immediate Timeout" parameter) the LTMR will wait to attempt to restart the motor.  The amount of time the LTMR waits before attempting restart is set via the "Auto restart delayed timeout" parameter.  Once a delayed restart occurs, the LTMR increments the "Auto Restart Delayed Count" by one.

Auto Restart Manual Count:  If a voltage dip occurs and the voltage remains low for a time greater than "Voltage Dip Restart timeout" then an auto restart will not occur.  It will be necessary to cycle the run command to the LTMR in order to restart.   The LTMR records the number of times this occurs under the parameter "Auto Restart Manual Count".

 

Schneider Electric Україна

Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:
Досліджуйте більше
Серія:

Потрібна допомога?

  • Почніть тут!

    Знайдіть відповіді зараз. Шукайте рішення самостійно або зверніться до нашого експерта.

  • Звернутися до служби підтримки

    Якщо вам потрібна допомога, додаткова інформація чи технічна підтримка або ви хочете подати скаргу, зв’яжіться з нашою командою з обслуговування клієнтів.

  • Де придбати?

    Зручний пошук найближчого дистриб’ютора, магазина або спеціалізованого партнера Schneider Electric у вашому регіоні.

  • Переглянути відповіді на поширені запитання

    Отримайте необхідну інформацію, переглянувши відповіді на поширені запитання за відповідними темами.

Я хочу отримувати новини й комерційну інформацію від компанії Schneider Electric і її дочірніх підприємств через електронні засоби зв’язку, зокрема електронною поштою. Я також даю згоду на збір інформації про мою взаємодію з отриманими електронними листами, зокрема відкриття й натискання елементів (через вбудовані в зображення приховані пікселі), для оцінки ефективності й удосконалення повідомлень. Щоб дізнатися більше, ознайомтеся з нашою Політикою конфіденційності.

  • Документація Продукції
  • Завантаження ПЗ
  • Інструмент вибору продукту
  • Заміна та заміна продукту
  • Контактний центр із надання довідки
  • Знайти наші представництва"
  • Де купити
  • Вакансії
  • Профіль компанії
  • Повідомити про проступок
  • Спеціальні можливості
  • Новини
  • Інвестори
  • Ecostruxure
  • Вакансії Пошук
  • Блог
  • Політика конфіденційності
  • Сповіщення про файли cookie
  • Умови користування
  • Change your cookie settings
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.