What are the minimum peripheral module firmware requirements for M580 Hot Standby?

Article available in these languages: Spanish

Below are the required minimum firmware versions in order to be compatible with a redundant M580 PAC.
ReferenceDescriptionMinimum Firmware Version
BMXCRA31200X80 Standard Drop Adapter2.14
BMXCRA31210X80 Performance Drop Adapter2.14
BMECRA31210X80 Performance Drop e-Adapter2.14
140CRA31200**Quantum Ethernet Drop Adapter2.14
BMENOC0301M580 Ethernet Scanner2.04
BMENOC0311M580 FactoryCast Ethernet Scanner2.04

Note: Though matching revisions is recommended, as long as the above minimum requirements are met, mixing versions is allowed. 
** Quantum drops are not supported with the BMEH582040.