Пошук серед найпопулярніших питань
How to find PLC and Memory load of BMED581020 PLC (IEC 61499) by application
You must used “MIBGET” function block.
Where is the list of “MIBGET” functionality?
For CPU load:
For Memory:
Example of application with CPU load:
Product line:
EAE, CPU load, Memory load, MIBGET, Simulator, BMED581020, IEC 61499
Environment:
Windows, EcoStruxure Automation Expert 22.0
Where is the list of “MIBGET” functionality?
For CPU load:
For Memory:
Example of application with CPU load:
- Add “MIBGET” function block like this
- Change parameter VALUE1 “STRING” to “UDINT” of “MIBGET” function block
- Save + Compile + deploy + RUN your application
- Generate event on REQ => result of value is 118 => CPU load = 11.8%
Product line:
EAE, CPU load, Memory load, MIBGET, Simulator, BMED581020, IEC 61499
Environment:
Windows, EcoStruxure Automation Expert 22.0
Опубліковано для:Schneider Electric Україна
Досліджуйте більше
Продукт:
Серія:
Досліджуйте більше
Продукт:
Серія: