Can I-line II busway be installed under a raised floor?
Issue:
Needs to install busway under a raised floor
Product Line:
Busway
Environment:
I-line II Busway
Cause:
N/A
Resolution:
Our I-Line II busway can be installed under "raised floors" as long as the busway joints and support system are accessible and the space is not used as return air systems.