What is the total heat loss of a Liquid Filled (Insulation Class "A") Power Distribution Transformer at various percentage loads?

The total heat loss of a Liquid Filled (Insulation Class "A") Power Distribution Transformer at various loads is calculated as follows :

At 100% load the total heat loss is the addition of the No Load Loss and the Load Loss

At X% load, the total heat loss is (X/100)² x Load Loss at 100% Load + No Load Loss

i.e. The No Load Loss is a constant loss and does not change with load
The Load Loss varies to the square of the per unit load

e.g. 1000kVA transformer with a No Load Loss of 1340 Watts and a Load Loss of 12500 Watts at 100% load and reference temperature of 75ºC, has the following losses at various loads

  • 100% Load       No Load Loss = 1340 Watts      Load Loss = (100/100)² x 12500 = 12500 Watts
  • 90% Load         No Load Loss = 1340 Watts      Load Loss = (90/100)² x 12500 = 10125 Watts
  • 80% Load         No Load Loss = 1340 Watts      Load Loss = (80/100)² x 12500 = 8000 Watts
  • 70% Load         No Load Loss = 1340 Watts      Load Loss = (70/100)² x 12500 = 6125 Watts
  • 60% Load         No Load Loss = 1340 Watts      Load Loss = (60/100)² x 12500 = 4500 Watts
  • 50% Load         No Load Loss = 1340 Watts      Load Loss = (50/100)² x 12500 = 3125 Watts

Schneider Electric UK

Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.