How do I pass the wire through the CT's to give the right inputs to the LUTM?
If the Schneider Electric CT's are used the following table and diagram show how the power cables should be placed.
Motor InPrimary (A)Secondary (A)No. of Pass(es)Reference
3.5 to 10.53013LUTC0301
5.2 to 163012LUTC0301
10.5 to 323011LUTC0301
17.5 to 535011LUCT0501
35 to 10510011LUCT1001
70 to 21020011LUTC2001
140 to 42040011LUTC4001
280 to 84080011LUTC8001