undefined undefined
{}

Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Where can I find the earth loop impedance (Zs) for the GV2 TeSys motor circuit breakers?
The charts below detail the Earth Loop impedance (Zs) for the GV2 range for any TN system based on the British Standard BS7671:2008+A3:2015

Two documents are also attached:
1) Sheet with Zs charts of TeSys motor circuit breakers:
  • TeSys GV2 (TeSys Deca - frame 2)
  • TeSys GV3 (TeSys Deca - frame 3)
  • TeSys GV4 (TeSys Deca - frame 4)
  • TeSys GV7
  • TeSys U (TeSys Ultra)
2) Explanation of the calculation of the maximum Earth Loop Impedance
This also includes additional information about:
  • Motor Rated devices
  • Ambient Temperature
TeSys GV2 Range
Please refer to the charts below that detail the maximum earth loop impedance Zs for 0.4s disconnection time with Uo 230V
 
GV2ME
ReferenceThermal Adjustment
Range In
Magnetic Tripping Current ImTolerance
Im+20%
Maximum Loop
Impedance Zs
 (A)(A)(A)(Ω) 
GV2ME010.1 .. 0.161.501.80121.39
GV2ME020.16 .. 0.252.402.8875.87
GV2ME030.25 .. 0.45.006.0036.42
GV2ME040.4 .. 0.638.009.6022.76
GV2ME050.63 .. 113.0015.6014.01
GV2ME061 .. 1.622.5027.008.09
GV2ME071.6 .. 2.533.5040.205.44
GV2ME082.5 .. 451.0061.203.57
GV2ME104 .. 6.378.0093.602.33
GV2ME146 .. 10138.00165.601.32
GV2ME169 .. 14170.00204.001.07
GV2ME2013 .. 18223.0267.60.82
GV2ME2117 .. 23327.0392.40.56
GV2ME2220 .. 25327.0392.40.56
GV2ME3224 .. 32416.0499.20.44
     
GV2P
ReferenceThermal Adjustment
Range In
Magnetic Tripping Current ImTolerance
Im+20%
Maximum Loop
Impedance Zs
 (A)(A)(A)(Ω) 
GV2P010.1 .. 0.161.501.80121.39
GV2P020.16 .. 0.252.402.8875.87
GV2P030.25 .. 0.45.006.0036.42
GV2P040.4 .. 0.638.009.6022.76
GV2P050.63 .. 113.0015.6014.01
GV2P061 .. 1.622.5027.008.09
GV2P071.6 .. 2.533.5040.205.44
GV2P082.5 .. 451.0061.203.57
GV2P104 .. 6.378.0093.602.33
GV2P146 .. 10138.00165.601.32
GV2P169 .. 14170.00204.001.07
GV2P2013 .. 18223.0267.60.82
GV2P2117 .. 23327.0392.40.56
GV2P2220 .. 25327.0392.40.56
GV2P3224 .. 32416.0499.20.44
     
GV2L
ReferenceThermal Adjustment
Range In
Magnetic Tripping Current ImTolerance
Im+20%
Maximum Loop
Impedance Zs
 (A)(A)(A)(Ω) 
GV2L030.45.006.0036.42
GV2L040.638.009.6022.76
GV2L05113.0015.6014.01
GV2L061.622.5027.008.09
GV2L072.533.5040.205.44
GV2L08451.0061.203.57
GV2L106.378.0093.602.33
GV2L1410138.00165.601.32
GV2L1614170.00204.001.07
GV2L2018223.0267.60.82
GV2L2225327.0392.40.56
GV2L3232416.0499.20.44
     
GV2LE
ReferenceThermal Adjustment
Range In
Magnetic Tripping Current ImTolerance
Im+20%
Maximum Loop
Impedance Zs
 (A)(A)(A)(Ω) 
GV2LE030.45.006.0036.42
GV2LE040.638.009.6022.76
GV2LE05113.0015.6014.01
GV2LE061.622.5027.008.09
GV2LE072.533.5040.205.44
GV2LE08451.0061.203.57
GV2LE106.378.0093.602.33
GV2LE1410138.00165.601.32
GV2LE1614170.00204.001.07
GV2LE2018223.0267.60.82
GV2LE2225327.0392.40.56
GV2LE3232416.0499.20.44
     
GV2RT
ReferenceThermal Adjustment
Range In
Magnetic Tripping Current ImTolerance
Im+20%
Maximum Loop
Impedance Zs
 (A)(A)(A)(Ω) 
GV2RT030.25 .. 0.48.009.6022.76
GV2RT040.4 .. 0.6313.0015.6014.01
GV2RT050.63 .. 122.0026.408.28
GV2RT061 .. 1.633.0039.605.52
GV2RT071.6 .. 2.551.0061.203.57
GV2RT082.5 .. 478.0093.602.33
GV2RT104 .. 6.3138.00165.601.32
GV2RT146 .. 10200.00240.000.91
GV2RT169 .. 14280.0336.00.65
GV2RT2013 .. 18400.0480.00.46
GV2RT2117 .. 23400.0480.00.46

Schneider Electric UK

Attachment(s)
Tesys Zs Values.pdf [139.87 KB]
Zs v201810.pdf [456.56 KB]
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.