Will GV2, GV3 and GV7 get de-rated with altitude? How will the de-rating work?

For GV2, GV3 and GV7:
Yes, for altitudes higher than 2000m, see below the de-rating on this table:
Altitude
Ue
Ie
≤ 2000m
1 (no de-rating)
1 (no de-rating)
2500 m
0,9
0,92
3000 m
0,8
0,90
3500 m
0,7
0,88
4000 m
0,6
0,86

For GV4, GV5 and GV6:
Yes, for altitudes higher than 2000m, see below the de-rating on this table:

GV4 GV5 GV6