What derating factors are applied to Tesys K, D, G contactors at altitude?

For contactors in the TeSys ranges (K, D & G) Please apply the following:

No derating below 3000m altitude for voltage and current in the power poles of the contactors.

Derating table for Tesys D contactors

For example, a LC1D80 at 5000m :

  • The maximum rated operational voltage is 1000V (IEC 947-4) and 690V (UL/CSA). At 5000m it becomes 1000V x 0.6 = 600V (IEC 947-4) and 690V x 0.6 = 414V (UL/CSA).
  • The maximum rated operational AC3 current is 80A at 5000m becomes 80A x 0.86 = 68A.

Schneider Electric UK

What derating factors are applied to Tesys K, D, G contactors at altitude?

For contactors in the TeSys ranges (K, D & G) Please apply the following:

No derating below 3000m altitude for voltage and current in the power poles of the contactors.

Derating table for Tesys D contactors

For example, a LC1D80 at 5000m :

  • The maximum rated operational voltage is 1000V (IEC 947-4) and 690V (UL/CSA). At 5000m it becomes 1000V x 0.6 = 600V (IEC 947-4) and 690V x 0.6 = 414V (UL/CSA).
  • The maximum rated operational AC3 current is 80A at 5000m becomes 80A x 0.86 = 68A.

Schneider Electric UK

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.