{}

Our Brands

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
APC Schneider Cooling Unit Identification

Article available in these languages: Spanish

Issue:
APC Cooling Unit identification.

Product line:
All Cooling Units.

Environment:
All Product models, all serial numbers.

Cause:
Nomenclature.

Resolution:

APC Unit Identification

FM Air/Water/Glycol
FMXXX-XXX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
FM35 (10T)

40 (12T)

50 (15T)
M= Main

E= Expansion
A= Air Cooled

E= Air Cooled
w/Multicool

W= Water Cooled

F= Water Cooled
w/Multicool

D= Water Cooled
w/Economizer

G= Glycol Cooled

B= Glycol Cooled
w/Multicool

P= Glycol Cooled
w/Economizer
BA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
E= Electric

W= Hot Water

S= Steam

H= Hot Gas

B= Hot Gas &
Electric

X= No Reheat
S=Replaceable
Steam Canister

C=Cleanable
Steam Canister

X=No Humidifier
D=Downflow

U=Upflow
(Front Return)

R=Upflow
(Rear Return)
FM-CW
FM40X-CXX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
FM40 (12T)
A= 3 row 20
Circuit coil

B= 4 row 20
Circuit coil

C= 4 row 40
Circuit coil
C= Chilled Water

BA=208-230/3/60

KA= 480/3/60

MA= 600/3/60

AA=208/208/3/60

CA=480/208/3/60

DA=480/480/3/60

EA=600/208/3/60
F= Electric
(High Output)

X= No Reheat
S= Replaceable
Steam Canister

C= Cleanable
Steam Canister

X= No Humidifier
D= Downflow

U= Upflow
(Front Return)

R= Upflow
(Rear Return)

IR
IR40-CXX-XXX
FM40M-CXX-XXX
ModelCapacity KWConfigurationVoltageReheatHumidifierAir Pattern
IR40 (12T)
C= Chilled Water

MA= 600/3/60

AA=208/208/3/60

CA=480/208/3/60

DA=480/480/3/60

EA=600/208/3/60
E= Electric

X= No Reheat
S= Steam Canister

X= No Humidifier
A= In-Row
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
FM40 (12T)
M= MainC= Chilled Water

MA= 600/3/60

AA=208/208/3/60

CA=480/208/3/60

DA=480/480/3/60

EA=600/208/3/60
E= Electric

X= No Reheat
S= Steam Canister

X= No Humidifier
A= In-Row

AFX (Not Current)
AFX-XXXM-XX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
AFX018 (5T)

065 (18T)
M= MainA= Air Cooled

W= Water Cooled

G= Glycol Cooled
BA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
E= Electric

X= No Reheat
S= Steam Canister

X= No Humidifier
D= Downflow

U= Upflow
(Front Return)
AFX (Not Current)
AFX-XX-XXX-X
ModelCapacity KWConfigurationVoltageAir Pattern
AFX20 (6T)

27 (8T)

34 (10T)

41 (12T)

48 (14T)

62 (18T)

70 (20T)

90 (26T)

98 (28T)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled
BA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
D= Downflow

U= Upflow
(Front Return)

R= Upflow
(Rear Return)











AFX (Not Current)
AFX-XXX-X-XX
Model# of BaysCapacity TonConfigurationVoltageAir Pattern
AFX1 =1 Bay

2 =2 Bay

3 =3 Bay
06 (1 Bay)

08 (1 Bay)

10 (2 Bay)

12 (2 Bay)

14 (2 Bay)

18 (2 Bay)

20 (3 Bay)

26 (3 Bay)

28 (3 Bay)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled
2=208-230/3/60

4= 480/3/60

6= 600/3/60
DF= Downflow

UD= Upflow
(Front or Rear Return)




CM (Not Current)
CM-XXX-X-XX-X
ModelCapacity KWConfigurationVoltageAir Pattern
CM003 (1T)

005 (1.5T)

007 (2T)

010 (3T)

014 (4T)

017 (5T)
A= Air Cooled

E= Air Cooled w/Multicool

R= Air Cooled w/Remote Condensing

W= Water Cooled

F= Water Cooled w/Multicool

G= Glycol Cooled

B= Glycol Cooled w/Multicool

P= Glycol Cooled w/Economizer

C= Chilled Water
BC=208-230/1/60

BA=208-230/3/60

FC=277/1/60

KA= 480/3/60
1-5T Air Cooled or
Self-Contained

1-3T Spot or Ducted

4-5T Ducted Only


S= Spot Cooled

D= Ducted
CM (Not Current)
CM-XX.X-X-XX-X-XX
ModelCapacity TonConfigurationVoltageAir PatternConfiguration
CM01.0

01.5

02.0

03.0

04.0

05.0
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

R= Remote Condensing

C= Chilled Water

P= Precool
BC=208-230/1/60

BA=208-230/3/60

FC=277/1/60

KA= 480/3/60
S= Spot Cooled

D= Ducted
SC= Air Cooled Self-Contained

IR= Air Cooled Indoor Condenser

IG= Air Cooled Indoor Condensing

OR= Air Cooled Outdoor Condenser

OG= Air Cooled Remote Indoor Condensing




CM (Not Current) (MBH is equal to 1000 BTU)
CMXX-XXX-XXXX
ModelCapacity MBHConfigurationVoltageConfigurationCompressor
Info
Air PatternConfiguration
CM15 (1T)

20 (1.5T)

25 (2T)

40 (3T)

50 (4T)

65 (5T)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

C= Chilled Water

E= Fan Coil/Evap
BC=208/1/60

DC=230/1/60

BA=208/3/60

FC=277/1/60

DA= 230/3/60
C= Closed Coupled

R= Remote
X= No Compressor

2= With Compressor
S= Spot Cooled

D= Ducted
E= ECWS

P= Precool
CM Condenser/Condensing Unit (Not Current) (MBH is equal to 1000 BTU)
CNXX-XXX-XXXX
ModelCapacity MBHConfigurationVoltageConfigurationConfigurationControl
CR= Condenser

CN= Condensing Unit

GD= Drycooler
15 (1T)

20 (1.5T)

25 (2T)

40 (3T)

50 (4T)

65 (5T)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled
DC=230/1/60

KC= 460/1/60
(FSC Only)

DA= 230/3/60

KA= 460/3/60
C= Closed Coupled

R= Remote
X= N/A

OP= Outdoor Propeller

IC= Indoor Centrifugal
C= Fan Cycle

F= Fan Speed

L= Flooded Control

X= N/A
CM Condenser/Condensing Unit/Drycooler (Not Current)
CM-XXX-XX.X-XXX-XX
ModelControlsCapacity TonAmbient TemperatureVoltage
CMAFL= Air Cooled Flooded

AFS= Air Cooled Fan Speed Control

GSS= Glycol Single Set Point

GDS= Glycol Dual Set Point
01.0

01.5

02.0

03.0

04.0

05.0
095= 95F

105= 105F

115= 115F
DC=230/1/60

KC= 460/1/60
(FSC Only)

DA= 230/3/60

KA= 460/3/60

CCT (Current)
CW100M-CXX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
CW100 (28T)
M= Main
C= Chilled WaterBA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
E= Electric

X= No Reheat
S= Steam Canister

X=No Humidifier
D=Downflow

U=Upflow
(Front Return)
CCT (Not Current)
CWXXX-CXX-X
ModelCapacity KWConfigurationVoltageAir Pattern
CW020 (6T)

027 (8T)

041 (12T)

050 (15T)

070 (20T)

087 (25T)

105 (30T)

123 (35T)

140 (40T)

175 (50T)

210 (60T)
C= Chilled WaterBA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
D=Downflow

U=Upflow
(Front Return)

R= Upflow
(Rear Return)

CCT (Not Current)
CW-XX.X-C-XX-X
ModelCapacity TonConfigurationVoltageAir Pattern
CW12.0

15.0

20.0

25.0

30.0

35.0

40.0

50.0

60.0
C= Chilled WaterBA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
D=Downflow

U=Upflow
(Front Return)

CCT (Not Current)
CCT-XX-XX
ModelCapacity TonConfigurationVoltage
CCT
12

15

20

25

30

35

40

50

60
C= Chilled Water2= 208, 220 or 230

4= 380, 415 or 460

6= 575














(DATAC) DTXX-CXX-XXX
Part Number or the CCT to the LEFTCapacity
Ton
ConfigurationVoltagePhase/FrequencyNot
Used
Not
Used
Air Pattern
DT12

15

20

25

30

35

40

50

60
C= Chilled WaterB= 208

C= 220

K= 460

M= 575

H= 415

D= 230

G= 380
A= 3/60

B= 3/50
XXU= Upflow

D= Downflow







































CCT (Not Current)
CCT( Capacity)-X(Voltage)X
ModelCapacity TonConfigurationVoltageConfiguration
CCTUnkownC= Chilled Water

A= Air Cooled

G= Glycol Cooled

W= Water Cooled

RC= Remote Condensing

ECWS= External Chilled Water Plus DX

CU= Mainframe Chiller System (4-30 ton in Air, Water, Glycol, PreFree Cool, and ECWS)

PC= PreFree Cool
2= 208, 220 or 230

4= 380, 415 or 460

6= 575
SC= Self-Contained







CCT (Not Current)
DX-XX.X-X-XX-X
ModelCapacity TonConfigurationVoltageAir Pattern
DX= Direct Expansion
06.0

08.0

10.0

15.0

20.0

24.0

30.0
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

R= Remote Condensing

P= Precool
BC=208-230/1/60

BA=208-230/3/60

KA= 480/3/60

MA= 600/3/60
D= Downflow

U= Upflow


SH (Not Current)
SH-X(X)
ModelVoltageConfiguration
SH= Sky-Hook
(Ceiling Mount Unit)
Capacity 1 ¾ Ton
2= 208-230/1/60

3= 277/1/60
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

C= Chilled Water
DH (Not Current)
DH-X(X)
ModelVoltageConfiguration
DH= Datahook
(Ceiling Mount Unit)
Capacity 2 ¾ Ton
2= 208-230/1/60

3= 277/1/60
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

TC (Not Current)
TC-XX.X-X-XX-X
ModelCapacity TonConfigurationVoltageAir Pattern
TC= TechCool
02.0(Not in C)

03.0 (Not in C)

05.0 (Not in C)

08.0 (All Config.)

10.0 (All Config.)

04.0 (C Only)

06.0 (C Only)

12.0 (C Only)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

R= Remote Condensing

P= Precool

C= Chilled Water
BA=208-230/3/60

KA= 460/3/60

MA= 6575/3/60
D= Downflow

U= Upflow


TC (Not Current)
TC-XX.X-X-XX-X
ModelCapacity TonConfigurationVoltageAir PatternSpecial
Features
TC= TechCool
2 (Not in C)

3 (Not in C)

5 (Not in C)

8 (All Config.)

10 (All Config.)

4 (C Only)

6 (C Only)

12 (C Only)
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

C= Chilled Water

E= Remote Condensing
2= 208, 220 or 230

4= 380, 415 or 460

6= 575
D=Downflow

UD=Upflow
PC= Precool (Only in 2, 3, & 5 Ton)

ECWS= External Chilled Water Supply
(TC Part Number) TCX-XXX-XXX
Part Number or the TC to the LEFTCapacity
Ton
ConfigurationVoltagePhase/FrequencySpecial
Features
Compressor
Info
Air Pattern
TC2

3

4

5

6

8

10

12
A= Air Cooled

W= Water Cooled

G= Glycol Cooled

C= Chilled Water

E= Remote Condensing
B= 208

C= 220

K= 460

M= 575

H= 415

D= 230

G= 380
A= 3/60

B= 3/50
X= none

P= Precool

E= ECWS
2= HermeticU= Upflow

D= Downflow

























NetworkAIR PA (Current)
ModelCapacity TonConfigurationVoltageAir PatternSpecial Features
PA1000
PA4000
.6t (1.5kW)
1.1t (3.9kW)
DX
DX
120
120
Horizontal
Horizontal
NEMA 5-15P  (692 Watts input)
NEMA 5-20P  (1610 Watts input)

NetworkAIR InRow Cooling (Current)
ModelCapacity TonConfigurationVoltageAir PatternSpecial Features
ACSC100
ACSC101

ACRC100
ACRC101
ACRC103

ACRP100
ACRP101
ACRP102

ACRP500
ACRP501
ACRP502
1.5t – 1.8t (5.30kW – 6.5kW)


3.75t - 8.75t  (13.2kW - 30.7kW)



6.5t – 10.4t (22.8kW - 36.6kW)



11.5t – 20.8t (40.8kW - 73.3kW)
DX  (R-410A)


CW



DX (R-407C)



CW
208 - 230
220 – 240

100 – 120
200 - 240
200 - 240

200 – 240
460 – 480
380 - 415

200 – 240
460 - 480
380 - 415
Horizontal


Horizontal



Horizontal



Horizontal
NEMA L6-20P  (2940 Watts input)


NEMA L5-20P  (1100 Watts input)
IEC-320-C14
IEC-309 16 A

4-wire (3PH + G) (13.737 kW input)
4-wire (3PH + G) (11.213 kW input)


4-wire (3PH + G) (3204 Watts input)
4-wire (3PH + G) (2054 Watts input)
NetworkAIR High-Density Cooling Enclosures
ModelCapacity TonConfigurationVoltageAir PatternSpecial Features
ARAC15000T5.1t (18kW)CW208HorizontalNEMA L6-20P  (2200 Watts input)

Schneider Electric UK

APC Schneider Cooling Unit Identification

Article available in these languages: Spanish

Issue:
APC Cooling Unit identification.

Product line:
All Cooling Units.

Environment:
All Product models, all serial numbers.

Cause:
Nomenclature.

Resolution:

APC Unit Identification
 
FM Air/Water/Glycol
            FMXXX-XXX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
FM35 (10T)
 
40 (12T)
 
50 (15T)
M= Main
 
E= Expansion
A= Air Cooled
 
E= Air Cooled
w/Multicool
 
W= Water Cooled
 
F= Water Cooled
w/Multicool
 
D= Water Cooled
w/Economizer
 
G= Glycol Cooled
 
B= Glycol Cooled
w/Multicool
 
P= Glycol Cooled
w/Economizer
BA=208-230/3/60
 
KA= 480/3/60
 
MA= 600/3/60
E= Electric
 
W= Hot Water
 
S= Steam
 
H= Hot Gas
 
B= Hot Gas &
Electric
 
X= No Reheat
S=Replaceable
Steam Canister
 
C=Cleanable
Steam Canister
 
X=No Humidifier
D=Downflow
 
U=Upflow
(Front Return)
 
R=Upflow
(Rear Return)
FM-CW
            FM40X-CXX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
FM40 (12T)
 
A= 3 row 20
Circuit coil
 
B= 4 row 20
Circuit coil
 
C= 4 row 40
Circuit coil
C= Chilled Water
 
 
BA=208-230/3/60
 
KA= 480/3/60
 
MA= 600/3/60
 
AA=208/208/3/60
 
CA=480/208/3/60
 
DA=480/480/3/60
 
EA=600/208/3/60
F= Electric
(High Output)
 
X= No Reheat
S= Replaceable
Steam Canister
 
C= Cleanable
Steam Canister
 
X= No Humidifier
D= Downflow
 
U= Upflow
(Front Return)
 
R= Upflow
(Rear Return)
 
IR
            IR40-CXX-XXX
            FM40M-CXX-XXX
ModelCapacity KWConfigurationVoltageReheatHumidifierAir Pattern
IR40 (12T)
 
C= Chilled Water
 
 
MA= 600/3/60
 
AA=208/208/3/60
 
CA=480/208/3/60
 
DA=480/480/3/60
 
EA=600/208/3/60
E= Electric
 
X= No Reheat
S= Steam Canister
 
X= No Humidifier
A= In-Row
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
FM40 (12T)
 
M= MainC= Chilled Water
 
 
MA= 600/3/60
 
AA=208/208/3/60
 
CA=480/208/3/60
 
DA=480/480/3/60
 
EA=600/208/3/60
E= Electric
 
X= No Reheat
S= Steam Canister
 
X= No Humidifier
A= In-Row
            
 
AFX (Not Current)
            AFX-XXXM-XX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
AFX018 (5T)
 
065 (18T)
 
M= MainA= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
BA=208-230/3/60
 
KA= 480/3/60
 
MA= 600/3/60
E= Electric
 
X= No Reheat
S= Steam Canister
 
X= No Humidifier
D= Downflow
 
U= Upflow
(Front Return)
 
AFX (Not Current)
            AFX-XX-XXX-X
ModelCapacity KWConfigurationVoltageAir Pattern
AFX20 (6T)
 
27 (8T)
 
34 (10T)
 
41 (12T)
 
48 (14T)
 
62 (18T)
 
70 (20T)
 
90 (26T)
 
98 (28T)
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
BA=208-230/3/60
 
KA= 480/3/60
 
MA= 600/3/60
 
D= Downflow
 
U= Upflow
(Front Return)
 
R= Upflow
(Rear Return)
 
 
 
 
 
 
 
 
 
 
 
AFX (Not Current)
            AFX-XXX-X-XX
Model# of BaysCapacity TonConfigurationVoltageAir Pattern
AFX1 =1 Bay
 
2 =2 Bay
 
3 =3 Bay
06 (1 Bay)
 
08 (1 Bay)
 
10 (2 Bay)
 
12 (2 Bay)
 
14 (2 Bay)
 
18 (2 Bay)
 
20 (3 Bay)
 
26 (3 Bay)
 
28 (3 Bay)
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
2=208-230/3/60
 
4= 480/3/60
 
6= 600/3/60
 
DF= Downflow
 
UD= Upflow
(Front or Rear Return)
 
 
 
 
 
CM (Not Current)
            CM-XXX-X-XX-X
ModelCapacity KWConfigurationVoltageAir Pattern
CM003 (1T)
 
005 (1.5T)
 
007 (2T)
 
010 (3T)
 
014 (4T)
 
017 (5T)
A= Air Cooled
 
E= Air Cooled w/Multicool
 
R= Air Cooled w/Remote Condensing
 
W= Water Cooled
 
F= Water Cooled w/Multicool
 
G= Glycol Cooled
 
B= Glycol Cooled w/Multicool
 
P= Glycol Cooled w/Economizer
 
C= Chilled Water
BC=208-230/1/60
 
BA=208-230/3/60
 
FC=277/1/60
 
KA= 480/3/60
 
 
1-5T Air Cooled or
Self-Contained
 
1-3T Spot or Ducted
 
4-5T Ducted Only
 
 

S= Spot Cooled
 
D= Ducted
 
CM (Not Current)
            CM-XX.X-X-XX-X-XX
ModelCapacity TonConfigurationVoltageAir PatternConfiguration
CM01.0
 
01.5
 
02.0
 
03.0
 
04.0
 
05.0
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
R= Remote Condensing
 
C= Chilled Water
 
P= Precool
BC=208-230/1/60
 
BA=208-230/3/60
 
FC=277/1/60
 
KA= 480/3/60
 
S= Spot Cooled
 
D= Ducted
 
SC= Air Cooled Self-Contained
 
IR= Air Cooled Indoor Condenser
 
IG= Air Cooled Indoor Condensing
 
OR= Air Cooled Outdoor Condenser
 
OG= Air Cooled Remote Indoor Condensing
 
 
 
 
CM (Not Current) (MBH is equal to 1000 BTU)
            CMXX-XXX-XXXX
ModelCapacity MBHConfigurationVoltageConfigurationCompressor
Info
Air PatternConfiguration
CM15 (1T)
 
20 (1.5T)
 
25 (2T)
 
40 (3T)
 
50 (4T)
 
65 (5T)
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
C= Chilled Water
 
E= Fan Coil/Evap
BC=208/1/60
 
DC=230/1/60
 
BA=208/3/60
 
FC=277/1/60
 
DA= 230/3/60
 
C= Closed Coupled
 
R= Remote
X= No Compressor
 
2= With Compressor
S= Spot Cooled
 
D= Ducted
 
E= ECWS
 
P= Precool
CM Condenser/Condensing Unit (Not Current) (MBH is equal to 1000 BTU)
            CNXX-XXX-XXXX
ModelCapacity MBHConfigurationVoltageConfigurationConfigurationControl
CR= Condenser
 
CN= Condensing Unit
 
GD= Drycooler
15 (1T)
 
20 (1.5T)
 
25 (2T)
 
40 (3T)
 
50 (4T)
 
65 (5T)
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
DC=230/1/60
 
KC= 460/1/60
(FSC Only)
 
DA= 230/3/60
 
KA= 460/3/60
C= Closed Coupled
 
R= Remote
X= N/A
 
OP= Outdoor Propeller
 
IC= Indoor Centrifugal
C= Fan Cycle
 
F= Fan Speed
 
L= Flooded Control
 
X= N/A
CM Condenser/Condensing Unit/Drycooler (Not Current)
            CM-XXX-XX.X-XXX-XX
ModelControlsCapacity TonAmbient TemperatureVoltage
CMAFL= Air Cooled Flooded
 
AFS= Air Cooled Fan Speed Control
 
GSS= Glycol Single Set Point
 
GDS= Glycol Dual Set Point
01.0
 
01.5
 
02.0
 
03.0
 
04.0
 
05.0
095= 95F
 
105= 105F
 
115= 115F
DC=230/1/60
 
KC= 460/1/60
(FSC Only)
 
DA= 230/3/60
 
KA= 460/3/60
 
CCT (Current)
            CW100M-CXX-XXX
ModelCapacity KWModuleConfigurationVoltageReheatHumidifierAir Pattern
CW100 (28T)
 
M= Main
 
C= Chilled WaterBA=208-230/3/60
 
KA= 480/3/60
 
MA= 600/3/60
E= Electric
 
X= No Reheat
S= Steam Canister
 
X=No Humidifier
D=Downflow
 
U=Upflow
(Front Return)
 
CCT (Not Current)
            CWXXX-CXX-X
ModelCapacity KWConfigurationVoltageAir Pattern
CW020 (6T)
 
027 (8T)
 
041 (12T)
 
050 (15T)
 
070 (20T)
 
087 (25T)
 
105 (30T)
 
123 (35T)
 
140 (40T)
 
175 (50T)
 
210 (60T)
C= Chilled WaterBA=208-230/3/60
 
KA= 480/3/60
 
MA= 600/3/60
D=Downflow
 
U=Upflow
(Front Return)
 
R= Upflow
(Rear Return)
 
 
CCT (Not Current)
            CW-XX.X-C-XX-X
ModelCapacity TonConfigurationVoltageAir Pattern
CW12.0
 
15.0
 
20.0
 
25.0
 
30.0
 
35.0
 
40.0
 
50.0
 
60.0
C= Chilled WaterBA=208-230/3/60
 
KA= 480/3/60
 
MA= 600/3/60
D=Downflow
 
U=Upflow
(Front Return)
 
 
CCT (Not Current)
            CCT-XX-XX
ModelCapacity TonConfigurationVoltage
CCT
 
12
 
15
 
20
 
25
 
30
 
35
 
40
 
50
 
60
C= Chilled Water2= 208, 220 or 230
 
4= 380, 415 or 460
 
6= 575
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
(DATAC) DTXX-CXX-XXX
Part Number or the CCT to the LEFTCapacity
Ton
ConfigurationVoltagePhase/FrequencyNot
Used
Not
Used
Air Pattern
DT12
 
15
 
20
 
25
 
30
 
35
 
40
 
50
 
60
C= Chilled WaterB= 208
 
C= 220
 
K= 460
 
M= 575
 
H= 415
 
D= 230
 
G= 380
A= 3/60
 
B= 3/50
XXU= Upflow
 
D= Downflow
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
CCT (Not Current)
            CCT( Capacity)-X(Voltage)X
ModelCapacity TonConfigurationVoltageConfiguration
CCTUnkownC= Chilled Water
 
A= Air Cooled
 
G= Glycol Cooled
 
W= Water Cooled
 
RC= Remote Condensing
 
ECWS= External Chilled Water Plus DX
 
CU= Mainframe Chiller System (4-30 ton in Air, Water, Glycol, PreFree Cool, and ECWS)
 
PC= PreFree Cool
2= 208, 220 or 230
 
4= 380, 415 or 460
 
6= 575
 
SC= Self-Contained
 
 
 
 
 
 
 
 
CCT (Not Current)
            DX-XX.X-X-XX-X
ModelCapacity TonConfigurationVoltageAir Pattern
DX= Direct Expansion
 
06.0
 
08.0
 
10.0
 
15.0
 
20.0
 
24.0
 
30.0
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
R= Remote Condensing
 
P= Precool
BC=208-230/1/60
 
BA=208-230/3/60
 
KA= 480/3/60
 
MA= 600/3/60
D= Downflow
 
U= Upflow
 
 
 
SH (Not Current)
            SH-X(X)
ModelVoltageConfiguration
SH= Sky-Hook
(Ceiling Mount Unit)
Capacity 1 ¾ Ton
2= 208-230/1/60
 
3= 277/1/60
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
C= Chilled Water
DH (Not Current)
            DH-X(X)
ModelVoltageConfiguration
DH= Datahook
(Ceiling Mount Unit)
Capacity 2 ¾ Ton
 
2= 208-230/1/60
 
3= 277/1/60
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
 
TC (Not Current)
            TC-XX.X-X-XX-X
ModelCapacity TonConfigurationVoltageAir Pattern
TC= TechCool
 
02.0(Not in C)
 
03.0 (Not in C)
 
05.0 (Not in C)
 
08.0 (All Config.)
 
10.0 (All Config.)
 
04.0 (C Only)
 
06.0 (C Only)
 
12.0 (C Only)
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
R= Remote Condensing
 
P= Precool
 
C= Chilled Water
BA=208-230/3/60
 
KA= 460/3/60
 
MA= 6575/3/60
D= Downflow
 
U= Upflow
 
 
 
TC (Not Current)
            TC-XX.X-X-XX-X
ModelCapacity TonConfigurationVoltageAir PatternSpecial
Features
TC= TechCool
 
2 (Not in C)
 
3 (Not in C)
 
5 (Not in C)
 
8 (All Config.)
 
10 (All Config.)
 
4 (C Only)
 
6 (C Only)
 
12 (C Only)
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
C= Chilled Water
 
E= Remote Condensing
2= 208, 220 or 230
 
4= 380, 415 or 460
 
6= 575
 
D=Downflow
 
UD=Upflow
 
PC= Precool (Only in 2, 3, & 5 Ton)
 
ECWS= External Chilled Water Supply
 
 
 
(TC Part Number) TCX-XXX-XXX
Part Number or the TC to the LEFTCapacity
Ton
ConfigurationVoltagePhase/FrequencySpecial
Features
Compressor
Info
Air Pattern
TC2
 
3
 
4
 
5
 
6
 
8
 
10
 
12
A= Air Cooled
 
W= Water Cooled
 
G= Glycol Cooled
 
C= Chilled Water
 
E= Remote Condensing
B= 208
 
C= 220
 
K= 460
 
M= 575
 
H= 415
 
D= 230
 
G= 380
A= 3/60
 
B= 3/50
X= none
 
P= Precool
 
E= ECWS
2= HermeticU= Upflow
 
D= Downflow
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
NetworkAIR PA (Current)
           
ModelCapacity TonConfigurationVoltageAir PatternSpecial Features
PA1000
PA4000
.6t (1.5kW)
1.1t (3.9kW)
DX
DX
120
120
Horizontal
Horizontal
 
NEMA 5-15P  (692 Watts input)
NEMA 5-20P  (1610 Watts input)
 
 
NetworkAIR InRow Cooling (Current)
           
ModelCapacity TonConfigurationVoltageAir PatternSpecial Features
ACSC100
ACSC101
 
ACRC100
ACRC101
ACRC103
 
ACRP100
ACRP101
ACRP102
 
ACRP500
ACRP501
ACRP502
 
1.5t – 1.8t (5.30kW – 6.5kW)
 
 
3.75t - 8.75t  (13.2kW - 30.7kW)
 
 
 
6.5t – 10.4t (22.8kW - 36.6kW)
 
 
 
11.5t – 20.8t (40.8kW - 73.3kW)
DX  (R-410A)
 
 
CW
 
 
 
DX (R-407C)
 
 
 
CW
208 - 230
220 – 240
 
100 – 120
200 - 240
200 - 240
 
200 – 240
460 – 480
380 - 415
 
200 – 240
460 - 480
380 - 415
Horizontal
 
 
Horizontal
 
 
 
Horizontal
 
 
 
Horizontal
NEMA L6-20P  (2940 Watts input)
 
 
NEMA L5-20P  (1100 Watts input)
IEC-320-C14
IEC-309 16 A
 
4-wire (3PH + G) (13.737 kW input)
4-wire (3PH + G) (11.213 kW input)
 
 
4-wire (3PH + G) (3204 Watts input)
4-wire (3PH + G) (2054 Watts input)
 
NetworkAIR High-Density Cooling Enclosures
ModelCapacity TonConfigurationVoltageAir PatternSpecial Features
ARAC15000T5.1t (18kW)CW208HorizontalNEMA L6-20P  (2200 Watts input)
 

Schneider Electric UK

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.