{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What is the maximum earth loop impedance Zs values for ILine MCCB SFAL & SFHL?

Please find attached the maximum earth loop impedance  Zs values for SFAL & SFHL MCCBs

In order to comply with BS7671 Amendment 3: 2015 the figures in the chart should be multiplied by Cmin .95

Zs Calculation


Zs - is the maximum earth fault loop impedance.
Uo - is the nominal voltage to earth (for a 400V 3 phase system this is 230V).
la - is the current causing the operation of the circuit breaker in less than 0.4 seconds.
Cmin is the minimum voltage factor to take account of voltage variations depending on time and place, changing of transformer taps and other considerations. (Cmin= 0.95)
in order to comply with BS7671 Amendment 3: 2015 the figure in the table should be multiplied by Cmin .95

Schneider Electric UK

Attachment(s)

Trip curve Zs SFAL,SFHL.pdfTrip curve Zs SFAL,SFHL.pdf [57.38 KB]
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: