Search FAQs
What is the procedure to reset the Altistart ATS22 back to factory default?
Issue:
How is the ATS22 reset back to factory default?
Product Line:
Altistart 22, ATS22
Environment:
All
Cause:
Resetting current settings back to the original factory settings.
Resolution:
Hold the ESC and UP arrows at the same time for 5 seconds, then the display will show the Utility menu - UtIL.
Push the enter button.
Use the arrow keys to scroll to parameter FCS, (Back to factory settings)
Push Enter once and you will get a prompt for "SUrE". Pushing the Enter button again will reset the soft starter back to factory defaults.
Released for:Schneider Electric UK
Explore more
Range:
Explore more
Range: