Why does the Quantum Unity PLC (140CPU43412A) timer reset on a power cycle?

The timer resets on a power cycle because the customer has made a Project Backup. When a Project backup is made, every power cycle
will cause a cold restart (%S0). This cold restart will reset all timers.