How do you add more then one Alarm Group to the Alarm Banner or Alarm Summary in Vijeo Designer?

In the Vijeo Designer Navigator right click on the Alarms and select "New Alarm Category"
image

Then add the Alarm Groups you want to display in the Alarm Banner or Alarm Summary,
Now Click OK
image2

Go to your Alarm Summary Settings or Alarm Banner Settings by double clicking on the Alarm Object on your Panel.
Then Select the Alarm Category instead of the Alarm Group. Then Click OK
image3

This Alarm Banner or Alarm Summary will now show the alarms from the Alarm Category you added to the Alarm display.

Schneider Electric UK

How do you add more then one Alarm Group to the Alarm Banner or Alarm Summary in Vijeo Designer?

In the Vijeo Designer Navigator right click on the Alarms and select "New Alarm Category"
image

Then add the Alarm Groups you want to display in the Alarm Banner or Alarm Summary,
Now Click OK
image2

Go to your Alarm Summary Settings or Alarm Banner Settings by double clicking on the Alarm Object on your Panel.
Then Select the Alarm Category instead of the Alarm Group. Then Click OK
image3

This Alarm Banner or Alarm Summary will now show the alarms from the Alarm Category you added to the Alarm display.

 

Schneider Electric UK

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.