Search FAQs
What AC powered inductive device can be used with a Quantum relay module?
Issue
How can I determine if an AC powered inductive device can be used with a Quantum relay module?
Product Line
Quantum
Resolution
Published VA ratings can be used to determine if a product may be used.
Maximum contact current is 2A for the 140DRA84000 and 5A for the 140DRC83000.
The maximum 120VAC load VA rating for the DRA module is 120 x 2 = 240VA.
The maximum 220VAC load VA rating for the DRA module is 220 x 2 = 440VA.
The maximum 120VAC load VA rating for the DRC module is 120 x 5 = 600VA.
The maximum 220VAC load VA rating for the DRC module is 220 x 5 = 1100VA.
Legacy KB System (APS) Data: RESL164212 V1.0, Originally authored by on , Last Edited by on
Related ranges: Modicon Quantum
Released for:Schneider Electric UK
Explore more
Range:
Explore more
Range: