Issue
This resolution describes how to wire 2-wire analog transmitters to the inputs of an STBACI1225 analog input module.
Product Line
Advantys STB
STBACI1225
Environment
Resolution
R2-wire analog transmitters require a loop power supply to power the loop. The following diagram shows how this is done with a single power supply for all current loops.
Released for:Schneider Electric UK

