{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Reporter generates Automation Error in pmlRepGen

Goals and Symptoms

Reporter shows automation error in PML Repgen
Report Status
Error reads:

  • Error -2147221080 (Automation error) has occurred in pmlRepGen

Causes and Fixes

This can be caused by incorrect database rights:

  1. Open SQL Management Console and expand the tree down to ION_Data > Users.
  2. In the right hand pane double click on Report to show properties.
    SQL user properties
  3. It should only have Public, db_datareader and ION_Reader checked.
  4. If you need to alter this cancel out of the above screens and expand the tree in the left hand pane and go to Security > Logins.
  5. Double click Reports in the right hand pane > Database Access tab> now edit the database role (to allow the three access rights mentioned in step #3).
    SQL properties

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: