{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Do redundant Modbus Plus cabling networks transmit and receive data on both cable A and B?

No. Although it is true that information is transmitted out on both cable A & B the receiving device will only listen to the information of the cable that gets there first. if the first transmission contains errors it will be ignored and the second cable will be used.


Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: