How can I use and cable the LO1 logic output of the ATS01?

Article available in these languages: Dutch

Output LO1 is an open collector NPN logic output.

The power supply for this output must be provided by an external source (24 VDC, min. 6 V, max. 30 V, max. current 200 mA).

Wiring

  • Connect the +24 VDC terminal on the external power supply to the load (plug-in relay or control relay, for example).
  • Connect the second load terminal to the LO1 terminal on the ATS.
  • Connect the COM terminal on the ATS to the 0 VDC on the external power supply.

LO1 Circuit diagram

Warning
If the load is inductive, use a freewheel diode on the load.

Schneider Electric UK

How can I use and cable the LO1 logic output of the ATS01?

Article available in these languages: Dutch

Output LO1 is an open collector NPN logic output.

The power supply for this output must be provided by an external source (24 VDC, min. 6 V, max. 30 V, max. current 200 mA).

Wiring

  • Connect the +24 VDC terminal on the external power supply to the load (plug-in relay or control relay, for example).
  • Connect the second load terminal to the LO1 terminal on the ATS.
  • Connect the COM terminal on the ATS to the 0 VDC on the external power supply.

LO1 Circuit diagram

Warning
If the load is inductive, use a freewheel diode on the load.
 

Schneider Electric UK

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.