Can a Modbus protocol be used to communicate between a Micrologic and a TSX PLC?
Yes, Modbus communication is possible between a Micrologic and a TSX PLC.  For an NT, NW or compact NS 800 to 3200 plug-in circuit breaker, the data tables are divided into 4 managers (3 for a fixed circuit breaker).

The four addresses (or the 4 slaves with linked addresses) are:
  • @ xx for the circuit breaker manager
  • @ xx +50 for the "chassis" manager
  • @ xx +100 for the "protection" manager
  • @ xx +200 for the "measurement" manager
Example:  A circuit breaker configured with address 21 has the circuit breaker manager at address 21 and the measurement manager at address 221, etc.  For communication with a PLC, the module used must be capable of managing the addresses up to 247.
Note:
This platform is discontinued. Please get access to our digital catalog https://digicat.se.com/ or contact our support center for more information about migrations to a newer platform.

Schneider Electric UK

Can a Modbus protocol be used to communicate between a Micrologic and a TSX PLC?
Yes, Modbus communication is possible between a Micrologic and a TSX PLC.  For an NT, NW or compact NS 800 to 3200 plug-in circuit breaker, the data tables are divided into 4 managers (3 for a fixed circuit breaker).

The four addresses (or the 4 slaves with linked addresses) are:
  • @ xx for the circuit breaker manager
  • @ xx +50 for the "chassis" manager
  • @ xx +100 for the "protection" manager
  • @ xx +200 for the "measurement" manager
Example:  A circuit breaker configured with address 21 has the circuit breaker manager at address 21 and the measurement manager at address 221, etc.  For communication with a PLC, the module used must be capable of managing the addresses up to 247.
 
Note:
This platform is discontinued. Please get access to our digital catalog https://digicat.se.com/ or contact our support center for more information about migrations to a newer platform.

Schneider Electric UK

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.