{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How can you program the R1 or R2 relays on the ATV31 or ATV312 drives?

Issue:
Programming the R1 or R2 on the ATV31/ATV312 drives.

Product Line:
ATV31 or ATV312

Environment:
All

Cause:
Setting up R1 and R2 relays on the ATV31 or ATV312 drives?

Resolution:
Note: "press Enter" means press in on the dial, and "scroll down" means turn the dial clockwise.

  1. While at RDY on the drive's display, press Enter
  2. Scroll down to I/O menu and press Enter
  3. Scroll down to R1, press enter, and choose your desired setting. Example: FLT is drive fault.
  4. Scroll down to R2 enter and choose your desired setting. Example: RUN is drive running.


For further detail, please refer to page 50 in the ATV312 Programming Manual.
https://www.se.com/ww/en/download/document/BBV46385/

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: