{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How do you include the initial values with a download in Unity Pro for a Premium PLC?

Product Line
Unity Pro, Premium

Resolution

To include the initial register values for a Unity Premium PLC with a download, the "Initialize %MWi on cold start" needs to be checked off under the processor configuration. To get to the configuration screen double-click on the processor under the project browser. The configuration screen will come up. Under the configuration tab there is a window called Operating Modes with five check boxes. Check off the "Initialize %MWi on cold start".

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: