{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How to change the relay configuration on an ATS22?
Issue:
Relay R1 and R2 programming on an ATS22

Product Line:
Altistart 22

Environment:
All

Cause:
Relay 1 or 2 needs a new assignment.

Resolution:
First, open access to the IO menu by going to the ConF menu, set LAC = ON.
Then go to the IO menu and set r1 or r2 to the appropriate configuration.

relay

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: