{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
Message "License not valid" appears in the “status” tab of a connected CANOpen slave and circles are orange instead of green in front of “CAN”, “CANopen_Optimized” and “[slave node]”:


3S.dat file is corrupted.
If possible please return the IMC card for analysis ("3S.dat file issue" should be mentionned in the return document)

If it is not possible to return the card :
Connect to the FTP server of the IMC card, delete 3S.dat file, switch off then on : 3S.dat will be generated again and CANOpen bus will run properly.

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: