What is the output voltage from the ATV212 RYA-RYC contact?
Issue:
Needs the output voltage from the ATV212 RYA-RYC contact

Product Line:
Altivar 212 ATV212

Environment:
All

Cause:
Status indication feedback

Resolution:
There is no drive output voltage from the RYA-RYC contact.  This is a dry contact.

Specs are as follows:
Minimum switching capacity: 3mA for 24Vdc
Maximum switching capacity:
resistive load 3A for 250Vac or 30Vdc
inductive load 2A for 250Vac or 30Vdc
Maximum response time: 7msec +- 0.5msec

Schneider Electric UK

What is the output voltage from the ATV212 RYA-RYC contact?
Issue:
Needs the output voltage from the ATV212 RYA-RYC contact

Product Line:
Altivar 212 ATV212 

Environment:
All
 
Cause:
Status indication feedback

Resolution:
There is no drive output voltage from the RYA-RYC contact.  This is a dry contact.

Specs are as follows:
Minimum switching capacity: 3mA for 24Vdc
Maximum switching capacity:
   resistive load 3A for 250Vac or 30Vdc
   inductive load 2A for 250Vac or 30Vdc
Maximum response time: 7msec +- 0.5msec

Schneider Electric UK

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.