What are the differences between a Flash EEPROM versus a SRAM memory card for the TSX Quantum or Premium controllers?
Issue:
What are the differences between a Flash EEPROM versus a SRAM memory card for the TSX Quantum or Premium controllers?

Product Line:
Quantum, Premium, Unity Pro

Resolution:
The flash EEPROM PCMCIA memory cards do not have volatile memory. You cannot make online changes. All program changes must be done offline
The SRAM PCMCIA memory cards is backed up by a battery but you can do online changes to the controller.