Issue:
How can ATS22 be programmed for a fixed number of starts per hour?
Product Line:
Altistart ATS22
Environment:
All
Cause:
Wants to delay the total number of times the softstarter can be started in one hour.
Resolution:
Programming:
Adj menu
Snb= number of starts Off or 1 thru 10
SLG= Start period 1 min thru 60 mins
Example= if Snb= 3 and SLG is 10 mins you can start and stop the drive 3 times in 10 mins. If you exceed the programmed start time the drive will trip out on SnbF.
How can ATS22 be programmed for a fixed number of starts per hour?
Product Line:
Altistart ATS22
Environment:
All
Cause:
Wants to delay the total number of times the softstarter can be started in one hour.
Resolution:
Programming:
Adj menu
Snb= number of starts Off or 1 thru 10
SLG= Start period 1 min thru 60 mins
Example= if Snb= 3 and SLG is 10 mins you can start and stop the drive 3 times in 10 mins. If you exceed the programmed start time the drive will trip out on SnbF.