Torque settings for NSX MCCB power terminals are below:
100amp and less rated frames = 10Nm
125-250amp rated frames = 15Nm
400-630amp rated frames = 50Nm
These are for the top and bottom power terminals
100amp and less rated frames = 10Nm
125-250amp rated frames = 15Nm
400-630amp rated frames = 50Nm
These are for the top and bottom power terminals