Search FAQs
How is the Start/Stop circuit wired for the ATS48 soft starter?
Issue:
Where do you wire the start run circuit for the ATS48 soft starter?
Product Line:
Altistart 48 ATS48
Environment:
All
Cause:
NA
Resolution:
For 2-wire control , jumper the RUN and STOP terminals and wire a run contact between the 24V and RUN terminals.
For 3-wire control, wire a N/C stop contact between 24V and STOP and wire a N/O start contact between 24V and RUN.
Where do you wire the start run circuit for the ATS48 soft starter?
Product Line:
Altistart 48 ATS48
Environment:
All
Cause:
NA
Resolution:
For 2-wire control , jumper the RUN and STOP terminals and wire a run contact between the 24V and RUN terminals.
For 3-wire control, wire a N/C stop contact between 24V and STOP and wire a N/O start contact between 24V and RUN.
Released for:Schneider Electric UK
Explore more
Range:
Explore more
Range: