Issue:
Is there a compatibility list of firmware for PL7 Micro/Premium processors?
Product Line:
TSXP57, TSX Premium, TSX37, TSX Micro, PL7, Firmware
Resolution:
Below is the compatibility table of firmware for the TSX Micro and Premium controllers:
TSX Micro hardware bases
---------------------------
Processor type PV Compatible operating systems versions
TSX3710000 =08 SV1.7
TSX3721000 =07 SV1.7
TSX3722000 =07 SV1.7
TSX3705001 <=06 SV3.5, SV4.0, SV5.0, SV5.1, SV6.0
TSX3708001 <=06 SV3.5, SV4.0, SV5.0, SV5.1, SV6.0
TSX3710001 <=08 SV3.0, SV3.5, SV4.0, SV5.0, SV5.1, SV6.0
TSX3721001 <=08 SV3.0, SV3.5, SV4.0, SV5.0, SV5.1, SV6.0
TSX3722001 <=08 SV3.0, SV3.5, SV4.0, SV5.0, SV5.1, SV6.0
TSX PREMIUM hardware bases
-----------------------------
Processor type PV Compatible operating systems versions
TSX P57102 <=08 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TSX P57102 = 10 SV4.1, SV4.2, SV4.3
TSX P57103 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P57153 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P57202, TSX P57252 <=08 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TSX P57202, TSX P57252 = 10 SV4.1, SV4.2, SV4.3
TSX P57203, TSX P57253 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P572623, TSX P572823 = 01 SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P57302, TSX P57352 <=08 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TSX P57302, TSX P57352 = 10 SV4.1, SV4.2, SV4.3
TSX P57303, TSX P57353 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P573623 = 01 SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P57402, TSX P57452 <= 08 SV3.1, SV3.4, SV3.6, SV3.7, SV3.8
TSX P57402, TSX P57452 = 09 SV4.1, SV4.2, SV4.3
TSX P57453 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P574823 = 01 SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TPMX P57102 <= 09 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TPMX P57102 = 11 SV4.1, SV4.2, SV4.3
TPMX P57202 <= 06 SV3.1, SV3.4, SV3.6, SV3.7, SV3.8
TPMX P57202 = 07 SV4.1, SV4.2, SV4.3
TPMX P57352 <= 07 SV3.1, SV3.4, SV3.6, SV3.7, SV3.8
TPMX P57352 = 08 SV4.1, SV4.2, SV4.3
TPMX P57452 <= 07 SV3.1, SV3.4, SV3.6, SV3.7, SV3.8
TPMX P57452 = 08 SV4.1, SV4.2, SV4.3
TPCX 571012 <= 08 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TPCX 573512 <= 09 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TPCX 57203 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TPCX 57353 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
Examples of operating systems files:
For a TSX MICRO TSX3721001 PLC, the compatible operating systems versions are SV3.0, SV3.5, SV4.0, SV5.0, SV5.1, SV6.0.
We recommend that you use version SV6.0 contained in the TSX_372x_V60.bin file.
For a TSX PREMIUM TSX57352 PLC version PV7, the compatible operating systems are SV3.1, SV3.4, SV3.6, SV3.7, and SV3.8.
We recommend that you use version SV3.8 contained in the TSX_57352_V38.BIN file.
Is there a compatibility list of firmware for PL7 Micro/Premium processors?
Product Line:
TSXP57, TSX Premium, TSX37, TSX Micro, PL7, Firmware
Resolution:
Below is the compatibility table of firmware for the TSX Micro and Premium controllers:
TSX Micro hardware bases
---------------------------
Processor type PV Compatible operating systems versions
TSX3710000 =08 SV1.7
TSX3721000 =07 SV1.7
TSX3722000 =07 SV1.7
TSX3705001 <=06 SV3.5, SV4.0, SV5.0, SV5.1, SV6.0
TSX3708001 <=06 SV3.5, SV4.0, SV5.0, SV5.1, SV6.0
TSX3710001 <=08 SV3.0, SV3.5, SV4.0, SV5.0, SV5.1, SV6.0
TSX3721001 <=08 SV3.0, SV3.5, SV4.0, SV5.0, SV5.1, SV6.0
TSX3722001 <=08 SV3.0, SV3.5, SV4.0, SV5.0, SV5.1, SV6.0
TSX PREMIUM hardware bases
-----------------------------
Processor type PV Compatible operating systems versions
TSX P57102 <=08 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TSX P57102 = 10 SV4.1, SV4.2, SV4.3
TSX P57103 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P57153 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P57202, TSX P57252 <=08 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TSX P57202, TSX P57252 = 10 SV4.1, SV4.2, SV4.3
TSX P57203, TSX P57253 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P572623, TSX P572823 = 01 SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P57302, TSX P57352 <=08 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TSX P57302, TSX P57352 = 10 SV4.1, SV4.2, SV4.3
TSX P57303, TSX P57353 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P573623 = 01 SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P57402, TSX P57452 <= 08 SV3.1, SV3.4, SV3.6, SV3.7, SV3.8
TSX P57402, TSX P57452 = 09 SV4.1, SV4.2, SV4.3
TSX P57453 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TSX P574823 = 01 SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TPMX P57102 <= 09 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TPMX P57102 = 11 SV4.1, SV4.2, SV4.3
TPMX P57202 <= 06 SV3.1, SV3.4, SV3.6, SV3.7, SV3.8
TPMX P57202 = 07 SV4.1, SV4.2, SV4.3
TPMX P57352 <= 07 SV3.1, SV3.4, SV3.6, SV3.7, SV3.8
TPMX P57352 = 08 SV4.1, SV4.2, SV4.3
TPMX P57452 <= 07 SV3.1, SV3.4, SV3.6, SV3.7, SV3.8
TPMX P57452 = 08 SV4.1, SV4.2, SV4.3
TPCX 571012 <= 08 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TPCX 573512 <= 09 SV3.0, SV3.4, SV3.5, SV3.6, SV3.7, SV3.8
TPCX 57203 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
TPCX 57353 = 01 SV5.0, SV5.1, SV5.2, SV5.3, SV5.4, SV5.5, SV5.6, SV5.7, SV5.8
Examples of operating systems files:
For a TSX MICRO TSX3721001 PLC, the compatible operating systems versions are SV3.0, SV3.5, SV4.0, SV5.0, SV5.1, SV6.0.
We recommend that you use version SV6.0 contained in the TSX_372x_V60.bin file.
For a TSX PREMIUM TSX57352 PLC version PV7, the compatible operating systems are SV3.1, SV3.4, SV3.6, SV3.7, and SV3.8.
We recommend that you use version SV3.8 contained in the TSX_57352_V38.BIN file.
Released for:Schneider Electric UK



