{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
How to read 64 bit modbus registers on 32 Bit Software Packages?
You must read the register in 4 x 16 Bit Pieces

Then apply the following formula to the values you receive in these 4 registers
(A*281474976710656+B*4294967296+C*65536+D)/1000


E.g. on the IEM3255 Meter 3204 3205 3206 & 3207 are used to read the Active Energy Total

A= 3204
B= 3205
C= 3206
D= 3207

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: