{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

Why do the new iC60H vigi units trip slower than the old Multi9 Vigi units?

It's normal that the ref A9V02763 trips in a longer time than the old multi9 MGV630304 because it's  A type vigi unit

This new RCD uses "ACCU" technology which is better on continuity of service however the tripping time is higher.

The ref 26665 "old Multi9" is AC type low continuity of service with "AD or CSP" technology !

If a tripping of less than 100ms is required then please use  MCB in conjunction with a AC type RCD.

Both must comply with BS61008

Schneider Electric UK

Explore more
Range:
Multi9Acti9 iC60Vigi for Acti9 iC60
Explore more
Range:
Multi9Acti9 iC60Vigi for Acti9 iC60
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.