What adaptation parts satisfy standard UL 60947-4-1 (Previously UL 508) type E on the GV2P and GV3P?

The adaptation parts to be used so that GV2P and GV3P circuit breakers comply with standard UL 60947-4-1 (previously UL 508) type E are detailed below.


GV2P circuit breakers

  • Order a GV2PxxH7(*) (except 32 A) circuit-breaker.
  • Add a "Large Spacing" adaptor, part number GV2H7. Without this adaptor, the protection will not be certified UL 508 Type E
Note: these parts are not available for purchase in the UK, this is for information only.
*The only difference between GV2PxxH7 and GV2Pxx circuit-breakers is their marking.

GV3P circuit breakers

  • Order a GV3Pxx circuit breaker
  • Add a "Large Spacing" cover, part number GV3G66 (to be placed on the power supply unit)
  • Add a signaling contact, part number GVAM11

GV3P with connection by lug-clamps

  • Order a GV3Pxx6 circuit-breaker
  • Add two IP20 covers, part number LAD96570
  • Add a signalling contact, part number GVAM11


GV4, GV5, GV6 and GV7

Whilst certified UL60947-4-1, these are not certified as self-protected circuit breakers for type E/F motor starters.

Additional Information

See attached Motor Control Solutions for the North American Market for further information.

Schneider Electric UK

Attachment(s)
Motor Control Solutions for the North American Market.pdf [2.45 MB]
What adaptation parts satisfy standard UL 60947-4-1 (Previously UL 508) type E on the GV2P and GV3P?

The adaptation parts to be used so that GV2P and GV3P circuit breakers comply with standard UL 60947-4-1 (previously UL 508) type E are detailed below.


GV2P circuit breakers

  • Order a GV2PxxH7(*) (except 32 A) circuit-breaker. 
  • Add a "Large Spacing" adaptor, part number GV2H7. Without this adaptor, the protection will not be certified UL 508 Type E
Note: these parts are not available for purchase in the UK, this is for information only.
*The only difference between GV2PxxH7 and GV2Pxx circuit-breakers is their marking.

GV3P circuit breakers

  • Order a GV3Pxx circuit breaker
  • Add a "Large Spacing" cover, part number GV3G66 (to be placed on the power supply unit)
  • Add a signaling contact, part number GVAM11

 

GV3P with connection by lug-clamps

  • Order a GV3Pxx6 circuit-breaker
  • Add two IP20 covers, part number LAD96570
  • Add a signalling contact, part number GVAM11


 

GV4, GV5, GV6 and GV7

Whilst certified UL60947-4-1, these are not certified as self-protected circuit breakers for type E/F motor starters. 
 

Additional Information

See attached Motor Control Solutions for the North American Market for further information.

Schneider Electric UK

Attachment(s)
Motor Control Solutions for the North American Market.pdf [2.45 MB]
Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.