Issue:
Assigning a logic input to external fault on the ATS48.
Product Line:
Altistart 48
Environment:
All Serial Numbers
Cause:
Logic input programming
Resolution:
To assign a logic input to external fault do the following:
From RDY
Press down to IO Menu, press enter
Press down to LIx (3 or 4), press enter
Press the down arrow to LIE (external fault), press enter
ESC back to RDY
When the logic input goes active to 24Vdc, the ATS48 will go to a faulted state and display EtF. After the logic input goes inactive to 0Vdc, a fault reset is required.
Assigning a logic input to external fault on the ATS48.
Product Line:
Altistart 48
Environment:
All Serial Numbers
Cause:
Logic input programming
Resolution:
To assign a logic input to external fault do the following:
From RDY
Press down to IO Menu, press enter
Press down to LIx (3 or 4), press enter
Press the down arrow to LIE (external fault), press enter
ESC back to RDY
When the logic input goes active to 24Vdc, the ATS48 will go to a faulted state and display EtF. After the logic input goes inactive to 0Vdc, a fault reset is required.
Released for:Schneider Electric UK

