Search FAQs
Where is the run command connected on the ATS01...FT?
Issue:
How is the run command wired to the ATS01...FT Altistart Softstart?
Product Line:
ATS01
Environment:
ATS01...FT
Cause:
Wire diagram not clear
Resolution:
External control voltage must be used.
If 110-240Vac control voltage is used. (can use the line voltage in the line inputs)
CL1/0 (neutral) and CL2 (120Vac) must be applied at the same time as line voltage.
If +24Vdc control voltage is used .
CL1/0 (-) and 24V (+) must be applied at the same time as line voltage.
Refer to manual catalog part number 8637CT0401
NOTE: A contactor or starter and overload protection are required with these softstarts.
How is the run command wired to the ATS01...FT Altistart Softstart?
Product Line:
ATS01
Environment:
ATS01...FT
Cause:
Wire diagram not clear
Resolution:
External control voltage must be used.
If 110-240Vac control voltage is used. (can use the line voltage in the line inputs)
CL1/0 (neutral) and CL2 (120Vac) must be applied at the same time as line voltage.
If +24Vdc control voltage is used .
CL1/0 (-) and 24V (+) must be applied at the same time as line voltage.
Refer to manual catalog part number 8637CT0401
NOTE: A contactor or starter and overload protection are required with these softstarts.
Released for:Schneider Electric UK
Explore more
Product:
Explore more
Product: