Issue
Not possible to save a configuration to the weighing module flash memory
Product Line
M580
Resolution
To save a configuration to the flash memory of the PMESWT0100 using the DFB, make sure that you ignore the DTM configuration (Ignore_DTM_configuration= 1), then set the initialization bit to 0 before saving to the flash memory (Saving_in_flash memory =1).
Not possible to save a configuration to the weighing module flash memory
Product Line
M580
Resolution
To save a configuration to the flash memory of the PMESWT0100 using the DFB, make sure that you ignore the DTM configuration (Ignore_DTM_configuration= 1), then set the initialization bit to 0 before saving to the flash memory (Saving_in_flash memory =1).