{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.
How can we help you today?
What can cause on OC1 fault on the ATV21 and ATV212 drives?
Issue:
OC1 fault on ATV21 and ATV212 drives

Product Line:
Altivar ATV21 and ATV212

Environment:
All

Cause:
Over current during acceleration

Resolution:
Increase the ACC time or the ACC2 time
Try adjusting the PT parameter
Enable catch on the fly F301= 4
Try adjusting the switching frequency F300
Set F316 parameter to 1 or 3

Schneider Electric UK

Explore more
Range:
Articles that might be helpful Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Explore more
Range: