{}

Our Brands

Impact-Company-Logo-English Black-01-177x54

Welcome to the Schneider Electric Website

Welcome to our website.

Search FAQs

What is the Maximum Zs earth fault loop impedance value for the TM30D trip unit?

For the NSX TM30D breakers at U=218.5V (This is including the Cmin Factor .95 as per BS7671 amendment 3:2015)

- Zs (5s) = 0.722 ohms
- Zs (0.4s) = 0.55 ohms

Schneider Electric UK

Explore more
Range:
ComPact NSX
Explore more
Range:
ComPact NSX
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.