Unity Pro, what is occurring on Save/Restore Data containing forced bit?
Saving data containing forced bit by the command «PLC/Save Data From PLC to file» save also the Forced state of these bit .
When these bit will be restored by the command «PLC/Restore Data From to file to PLC»  they will be restored in Forced state.
Nevertheless the list of forced bit will not be restored and in final bit will be forced in the application without knowing easily which ones.
So it is strongly recommended to do not save data with forced bit in the application.

This behavior is always present in Unity Pro V11.1  it is planned to be fixed in a next version.

Schneider Electric UK

Unity Pro, what is occurring on Save/Restore Data containing forced bit?
Saving data containing forced bit by the command «PLC/Save Data From PLC to file» save also the Forced state of these bit .
When these bit will be restored by the command «PLC/Restore Data From to file to PLC»  they will be restored in Forced state.
Nevertheless the list of forced bit will not be restored and in final bit will be forced in the application without knowing easily which ones.
So it is strongly recommended to do not save data with forced bit in the application.

This behavior is always present in Unity Pro V11.1  it is planned to be fixed in a next version.
 

Schneider Electric UK

Explore more
Range:
Explore more
Range:
Users group

Discuss this topic with experts

Visit our Community for first-hand insights from experts and peers on this topic and more.
Users group

Discuss this topic with experts

Visit our community and get advice from experts and peers on this topic and more
Explore more
Range:
Explore more
Range:
move-arrow-top
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.