Issue:
This document will describe how to change the Date on Time on a Network Air FM unit.

Product line:
FM 35-50, IR40, ACFM400, ACFM200.

Environment:
All Serial Numbers.

Cause:
Install, Configuration.

Resolution:

  1. How to change the Date on Time on a Network Air FM unit.
  2. Press the ESC Key until you get to the main menu.
  3. Press ENTER on Setup.
  4. Press ENTER on System 1.
  5. Press ENTER on Display.
  6. Press ENTER on Date/Time.
  7. Press ENTER on Date to change Date and now you will need to enter a password.
  8. The default password is 7852 Select each number and then press ENTER to move to the next one.
  9. Press ENTER on Date again.
  10. Select Day, Month, and then Year and Press ENTER.
  11. Press ENTER after changing the Year.
  12. Press the DOWN arrow and then ENTER to change the TIME.
  13. Finish by pressing the ENTER key and then press ESC until you get to the status menu.