Issue:
Program relays for the ATV930
Product Line:
Altivar 930
Environment:
All
Cause:
N/A
Resolution:
Under main menu, go into menu 5 complete settings.
Go into menu 5.11 Input/Output.
Go into the relay configuration tab.
Enter on each relay and change assignment as needed.
Program relays for the ATV930
Product Line:
Altivar 930
Environment:
All
Cause:
N/A
Resolution:
Under main menu, go into menu 5 complete settings.
Go into menu 5.11 Input/Output.
Go into the relay configuration tab.
Enter on each relay and change assignment as needed.
Released for:Schneider Electric UK

