Video: How to change a Cooling Set point on a push button Uniflair display
Issue:
How to change a cooling set point on a Uniflair Unit.

Product line:
All Uniflair Units with Push-Button Display, All Chilled Water Uniflairs.

Environment:
All Serial Number with Push-Button Units.

Cause:
Repair, Install, Maintenance.

Resolution

How to change a Cooling Set point on a push button Uniflair display.

Press <> PRG.

Settings Menu <> ENTER.

Code <> 00000 ENTER.

Operative settings <> ENTER.

Press ENTER again to the cooling set point.

Use the Arrows to set the correct temperature.

Press ENTER twice and then ESC back out to the main menu.